[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-807678":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":22},807678,450,1,"单选题","某加氢装置检修结束转入开工操作,当系统压力升至13MPa,反应器入口温度升至180℃时发现高压换热器底部排污导淋崩掉,大量氢气泄漏着火,装置进行紧急泄压处理。针对这起事故应采取的预防措施不正确是()。",[11,15,18],{"key":12,"text":13,"correct":14},"A","停工期间对高压临氢部位注碱清洗",false,{"key":16,"text":17,"correct":14},"B","加强原料油和氢气中氯离子含量监控",{"key":19,"text":20,"correct":21},"C","排污导淋崩掉属于工艺氯离子腐蚀,跟设备材质无关",true,"",{"id":6,"name":24,"category":25,"favorite":26},"加氢工艺","特种作业",0]