[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-716167":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},716167,390,3,"判断题","更换成组的电压互感器时,还应对并列运行的电压互感器检查其连接组别,并核对相位。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"对运行中的电压互感器及其二次线需要更换时，除应按照相关的安全工作规程的规定执行外，还应特别注意以下几点：l)个别电压互感器在运行中损坏需要更换时，应选用电压等级与电网运行电压相符、变比与原来的相同、极性正确、励磁特性相近的电压互感器，并需经试验合格；2)更换成组的电压互感器时，除应注意上述内容外，对于二次与其他电压互感器并列运行的还应检查其接线组别并核对相位；3)电压互感器二次线更换后，应进行必要的核对，防止造成错误接线；4)电压互感器及二次线更换后必须测定极性。",{"id":6,"name":21,"category":22,"favorite":23},"高压电工","特种作业",0]