[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-716039":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},716039,390,3,"判断题","在进行全站停电操作时,应先将电容器组的开关断开,然后再停各分路的出线开关。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"在进行全站停电操作时，若先拉各路出线开关，负荷减小，系统立即过补，此时若系统中存在谐波，可能会导致谐波电流放大，烧毁系统设备。另外电容器会抬高系统电压，即所说的“容升”现象，那么未切除的部分负荷会有过电压的危险，影响使用寿命甚至烧毁用电设备。所以在进行全站停电操作时，应先将电容器组的开关断开，然后再停各分路的出线开关。",{"id":6,"name":21,"category":22,"favorite":23},"高压电工","特种作业",0]