[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-715264":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":22},715264,390,1,"单选题","2000kW及以上大容量的高压电机,普遍采用()代替电流速断保护。",[11,15,19],{"key":12,"text":13,"correct":14},"A","过负荷保护",false,{"key":16,"text":17,"correct":18},"B","纵差动保护",true,{"key":20,"text":21,"correct":14},"C","低电压保护","高压电动机一般应装设什么保护? 1）电流速断保护－－电动机定子绕组相间短路的保护，一般用于2000kW以下的电动机，动作于跳闸． 2）纵联差动保护－－对于2000kW及以上的电动机，或2000kW以下电动机的电流速断保护的灵敏度满足不了要求时，采用差动保护来对电动机内部及引出线相间短路进行保护，动作于跳闸． 3）过负载保护－－预防电动机所拖动的生产机械过负荷而引起的过电流，动作于信号或带一定时限动作于跳闸. 4）单相接地保护－－在小接地电流系统中，当接地电流大于5A时，为预防电流电动机定子绕组单相接地故障的危害，必须装设单相接地保护，接地电流值为5A～10A时，动作于信号；接地电流大于10A时，动作于跳闸． 5）低电压保护－－防止电压降低或中断电动机自启动的保护，动作于跳闸，可根据需要装设。",{"id":6,"name":24,"category":25,"favorite":26},"高压电工","特种作业",0]