[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-715149":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":22},715149,390,1,"单选题","中性点不接地的电力系统中,用电设备的绝缘水平应按()考虑。",[11,15,18],{"key":12,"text":13,"correct":14},"A","相电压",false,{"key":16,"text":17,"correct":14},"B","2倍相电压",{"key":19,"text":20,"correct":21},"C","线电压",true,"中性点不接地系统是指电力系统中性点不接地。中性点不接地系统发生单相接地故障时，中性点电压发生位移，但是三相之间的线电压仍然保持对称，且数值不变；由于没有直接的短路通路，接地故障电流由线路和设备对地分布电容回路提供，是容性电流，通常数值不大，一般不需要立即停电，可以带故障运行一段时间（一般不超过2h）；但非故障相对地电压升高，数值最大为额定相电压的1.73倍，因此用电设备的绝缘水平需要按线电压考虑。",{"id":6,"name":24,"category":25,"favorite":26},"高压电工","特种作业",0]