[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-715103":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":22},715103,390,1,"单选题","继电保护的()是指保护快速切除故障的性能。",[11,15,19],{"key":12,"text":13,"correct":14},"A","速动性",true,{"key":16,"text":17,"correct":18},"B","选择性",false,{"key":20,"text":21,"correct":18},"C","可靠性","速动性是指继电保护装置应能尽快地切除故障，以减少设备及用户在大电流、低电压运行的时间，降低设备的损坏程度，提高系统并列运行的稳定性。一般必须快速切除的故障有：(1) 使发电厂或重要用户的母线电压低于有效值(一般为0.7倍额定电压)。(2) 大容量的发电机、变压器和电动机内部故障。(3) 中、低压线路导线截面过小，为避免过热不允许延时切除的故障。(4) 可能危及人身安全、对通信系统造成强烈干扰的故障。故障切除时间包括保护装置和断路器动作时间，一般快速保护的动作时间为0.04s～0.08s，最快的可达0.01s～0.04s，一般断路器的跳闸时间为0.06s～0.15s，最快的可达0.02s～0.06s。对于反应不正常运行情况的继电保护装置，一般不要求快速动作，而应按照选择性的条件，带延时地发出信号。",{"id":6,"name":24,"category":25,"favorite":26},"高压电工","特种作业",0]