[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-715080":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":22},715080,390,1,"单选题","变压器运行时各部件的温度是不同的,()温度最高。",[11,15,19],{"key":12,"text":13,"correct":14},"A","铁芯",false,{"key":16,"text":17,"correct":18},"B","绕组",true,{"key":20,"text":21,"correct":14},"C","变压器油","变压器运行时，绕组的温度最高，绝缘油的温度最低，各部位的温度不同。变压器运行时各部分的温度是不相同的。线圈的温度最高，其次是铁芯的温度，绝缘油温度低于线圈和铁芯的温度。变压器的上部油温高于下部油温。变压器运行中的允许温度按上层油温来检查。对于A 级绝缘的变压器在正常运行中，当周围空气温度最高为40℃时，变压器绕组的极限工作温度105℃。由于绕组的温度比油温度高10℃，为防止油质劣化，规定变压器上层油温最高不超过95℃，而在正常情况下，为防止绝缘油过速氧化，上层油温不应超过85℃。对于采用强迫油循环水冷却和风冷的变压器，上层油温不宜经常超过75℃。所以，变压器在运行过程中，工作人员一定要注意变压器温度的变化，避免温度过高对变压器造成的损坏。",{"id":6,"name":24,"category":25,"favorite":26},"高压电工","特种作业",0]