[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-711584":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},711584,377,3,"判断题","断路器在选用时，要求线路末端单相对地短路电流要大于或等于1.25倍断路器的瞬时脱扣器整定电流。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"线路末端单相对地短路电流大于或等于1.25倍断路器瞬时(或短延时)脱扣器整定电流。这对负载电流较小，配电线路较长的情况尤为重要。因为线路较长时，末端短路电流较小，单相对地短路电流就更小。在三相四线制中相零短路时，对地短路电流还要小些，有时比道电流脱扣器整定的电流还要小，不能使过电流脱扣器动作，因而在单相对地时失去保护。",{"id":6,"name":21,"category":22,"favorite":23},"低压电工","特种作业",0]