[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-604560":3},{"question":4,"library":33},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":31,"analysis":32},604560,303,2,"多选题","某矿综采工作面试运行期间,采煤机工作中电磁启动器跳闸。经查,接触器电磁铁线圈均匀烧毁;更换电磁铁线圈后,经7~8h又发生相同故障;再次更换电磁铁线圈,故障重复发生。工作面其他同型电磁启动器工作正常。经分析,该故障为启动器电磁系统故障。其发生的原因可能为()。",[11,15,18,22,25,28],{"key":12,"text":13,"correct":14},"A","电磁系统中,磁力线圈匝数过少",false,{"key":16,"text":17,"correct":14},"B","电磁系统中,磁力线圈匝数过多",{"key":19,"text":20,"correct":21},"C","电磁系统中,活动电磁铁被卡阻,造成气隙过大",true,{"key":23,"text":24,"correct":14},"D","电磁系统中,活动电磁铁闭合位置预留气隙过小",{"key":26,"text":27,"correct":21},"E","电磁系统中,活动电磁铁闭合位置预留气隙过大",{"key":29,"text":30,"correct":21},"F","电磁启动器安装调试中,未按规定检查电磁系统","CEF","",{"id":6,"name":34,"category":35,"favorite":36},"煤矿井下电气作业","安全生产",0]