[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-422437":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},422437,197,2,"多选题","电力系统并列运行暂态稳定性分析中不考虑非周期分量、负序分量和零序分量的影响，错误原因是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","认为非周期分量，负序分量和零序分量都已衰减到零",true,{"key":16,"text":17,"correct":14},"B","负序分量和零序分量都已衰减到零，非周期分量电流对转子的平均电磁转矩为零",{"key":19,"text":20,"correct":21},"C","非周期分量已衰减到零，即使流入发电机定子绕组也不会在发电机气隙中产生电枢反应磁通",false,{"key":23,"text":24,"correct":14},"D","非周期分量，负序分量和零序分量都不会在发电机气隙中产生电枢反应磁通，所以对发电机转子的运动无影响","ABD","负序电流产生的磁场的旋转方向与转子旋转方向相反，其与转子绕组电流形成的磁场相互作用产生的转矩主要是以两倍同步频率交变的、平均值近似为零的制动转矩，且转子机械惯性较大，其对电力系统的机电暂态过程影响很小。对于零序电流来说由于连接发电机的升压变压器绝大多数采用△-星形连接，发电机接在三角形侧，故障发生在高压网络时，零序电流不通过发电机。即使有零序电流流过发电机，由于零序电流在转子空间的合成磁场为零，不产生转矩，不会对电力系统的机电暂态过程造成影响，完全可略去。",{"id":6,"name":28,"category":29,"favorite":30},"电工类 (电网)","公务员",0]