[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-422414":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},422414,197,2,"多选题","500 KV线路装设高压并联电抗器应考虑的条件有（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","在500 KV电网中，正常及检修运行方式下，发生故障或任一处无故障三相跳闸时，必须采取措施限制母线侧及线路侧的过电压",true,{"key":16,"text":17,"correct":14},"B","需要采用高压并联电抗器并带中性点小电抗作为解决潜供电流的措施时",{"key":19,"text":20,"correct":14},"C","发电厂为无功平衡需要，而又无法装设低压电抗器时",{"key":22,"text":23,"correct":14},"D","系统运行操作（如同期并列）需要时","ABCD","500 KV线路装设高压并联电抗器应考虑的条件有：（1）在500 KV电网各发展阶段中，正常及检修（送变电单一元件）运行方式下，发生故障或任一处无故障三相跳闸时，必须采取措施限制母线及线路侧的工频过电压在最高线路运行电压的1.3至1.4倍额定值以下时；（2）为保证线路瞬时性单相故障时单相重合成功，经过比较，如认为需要采用高压并联电抗器并带中性点小电抗作为解决潜供电流的措施时；（3）发电厂为无功平衡需要，而又无法装设低压电抗器时；（4）系统运行操作（如同期并列）需要时。",{"id":6,"name":27,"category":28,"favorite":29},"电工类 (电网)","公务员",0]