[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-422046":3},{"question":4,"library":27},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":25,"analysis":26},422046,197,2,"多选题","电流互感器二次回路接地点的错误的设置方式是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","所有的电流互感器二次回路接地点均设置在电流互感器端子箱",true,{"key":16,"text":17,"correct":14},"B","每只电流互感器二次回路必须有一个单独的接地点",{"key":19,"text":20,"correct":21},"C","电流互感器二次接地点只允许有一个，对于多组电流互感器相互有联系的二次回路接线点应设置在保护盘上",false,{"key":23,"text":24,"correct":21},"D","以上说法均正确","AB","电流互感器的基本作用是信号变换和隔离。正因为有隔离，因此，二次回路在接地前是浮地系统，也就是说，其电位与地电位没有固定关系。单点接地相当于给接地点一个参考电位，并不形成回路，不会短路，也不会影响测量。如果多点接地，且接地前，这些接地点之间有电位差，那么，接地后就会形成回路，相当于短路，将造成测量结果错误。电流互感器二次回路接地点设置在电流互感器端子箱。",{"id":6,"name":28,"category":29,"favorite":30},"电工类 (电网)","公务员",0]