[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-422041":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":24,"analysis":25},422041,197,2,"多选题","分相电流差动保护的特点有哪些（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","能明确区别内部和外部故障",true,{"key":16,"text":17,"correct":14},"B","具有自选相功能",{"key":19,"text":20,"correct":14},"C","不受系统运行方式的影响",{"key":22,"text":23,"correct":14},"D","不能作为后备保护","ABCD","优点：（1）以基尔霍夫电流定律为判断故障的依据，原理简单可靠，动作速度快。（2）具有天然的选相能力。（3）不受系统振荡、非全相运行的影响，可以反映各种类型的故障，是理想的线路主保护。（4）能明确区别内部和外部故障。缺点：（1）要求保护装置通过光纤通道所传送的信息具有同步性。（2）对于超高压长距离输电线路，需要考虑电容电流的影响。（3）线路经大电阻接地或重负荷、长距离输电线路远端故障时，保护灵敏度会降低。",{"id":6,"name":27,"category":28,"favorite":29},"电工类 (电网)","公务员",0]