[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-421136":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},421136,197,1,"单选题","以下（ ）不配置电压互感器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","主母线",false,{"key":16,"text":17,"correct":18},"B","旁路母线",true,{"key":20,"text":21,"correct":14},"C","发电机出现端部",{"key":23,"text":24,"correct":14},"D","系统同期点","电压互感器有如下几个配置原则。（1）母线：除旁路母线外，一般工作母线及备用母线都装有一组电压互感器。（2）线路：35kV及以上输电线路，当对端有电源时，装有一台单向电压互感器。（3）发电机：一般装2～3组电压互感器，一组（三只单相、双绕组）供自动调节励磁装置，另一组供测量仪表、同期和保护装置使用。（4）变压器：变压器低压侧有时为了满足同期或继电保护的要求，设有一组电压互感器。",{"id":6,"name":27,"category":28,"favorite":29},"电工类 (电网)","公务员",0]