[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-389608":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},389608,172,1,"单选题","机房室外安装的安全防范监控系统设备应采取防雷电保护措施，电源线、信号线应采用屏蔽电缆，避雷装置和电缆屏蔽层应接地，且接地电阻值不应大于 （ ） ?。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10",true,{"key":16,"text":17,"correct":18},"B","50",false,{"key":20,"text":21,"correct":18},"C","20",{"key":23,"text":24,"correct":18},"D","1","计算机机房应采用如下四种接地方式：防雷接地时电阻值不应该大于10?，交流工作接地时电阻值不应大于4?，安全工作接地时电阻值不应大于4?，直流工作接地时电阻值不应大于1?。",{"id":6,"name":27,"category":28,"favorite":29},"(高级)信息系统项目管理师","职业资格",0]